Product Type A*RDM*F

Product Type ARDMF

IP RATING:

IP66 & IP68 (50 metres – 7 Days), Type 4X

OPERATING TEMP:

Neoprene Seals -35°C to +90°C
Silicone Seals -60°C to +180°C

MATERIALS:

Aluminium, Brass or Stainless Steel

PLATING:

Electroless Nickel

DESCRIPTION

“A*RDM” type glands are certified Flameproof Ex db, Increased Safety Ex eb, Restricted Breathing Ex nR and Dust Protected Ex ta. They are suitable for use in Zone 1 and 2 for Gas Groups IIA, IIB and IIC and additionally for use in Zones 20, 21 and 22 for Dust Groups IIIA, IIIB and IIIC. They provide two controlled pull resistant environmental displacement seals on the cable outer sheath, minimising damage to cables that exhibit “cold flow” characteristics. The gland maintains IP66 & IP68 to 50 metres and is supplied with an IP O-ring seal as standard on metric entry threads. The gland features a freely rotating male threaded conduit connection for ease of installation.

COMPLIANCE STANDARDS:

EN 60079-0, EN 60079-1, EN 60079-7, EN 60079-15, EN 60079-31 IEC 60079-0, IEC 60079-1, IEC 60079-7, IEC 60079-31 & IEC 60529 UL514B, UL1203, UL2225, UL50E, ANSI/UL 60079-0/7, ISA 60079-31

CERTIFICATION:

ATEX
II 1D 2G Ex db IIC Gb / Ex eb IIC Gb / Ex ta IIIC Da
II 3G Ex nR IIC Gc
UKEX
II 1D 2G Ex db IIC Gb / Ex eb IIC Gb / Ex ta IIIC Da
II 3G Ex nR IIC Gc
IECEx
Ex db IIC Gb / Ex eb IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da
CEC – Canada
Ex db IIC Gb / Ex eb IIC Gb / Ex ta IIIC Da
Class II Group E, F & G
Class III Type 4X
NEC – USA
Class I Zone 1 AEx eb IIC Gb / Zone 20 AEx ta IIIC Da
Class II Group E, F & G
Class III Type 4X
EAC – Russia
1Ex db IIC Gb X / 1Ex eb IIC Gb X / 2Ex nR IIC Gc X / Ex ta IIIC Da X

INMETRO – Brazil
Ex db IIC Gb / Ex eb IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da
CCC – China
Ex d IIC Gb / Ex e IIC Gb / Ex nR IIC Gc / Ex tD A20
UKRAINE
II 2G Ex db IIC Gb / II 2G Ex eb IIC Gb / II 3G Ex nR IIC Gc / II 1D Ex ta IIIC Da
CCoE – India
Ex db IIC Gb / Ex eb IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da
ECAS-Ex – U.A.E
Ex db IIC Gb / Ex eb IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da
ABS
Specified ABS Rules
LLOYD’S
Ex db IIC Gb / Ex eb IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da
DNV
Ex db IIC Gb / Ex eb IIC Gb / Ex nR IIC Gc / Ex ta IIIC Da

Installation

Instructions – English
PA119 AxRDMxx
Instructions – Portuguese
PA419 AxRDMxx
Instructions – Russian
PA728 AxRDMxx
Instructions – Chinese
PA828 AxRDMxx

Drawings

Training & Learning Knowledge Centre

Designed for engineers, installers, and specifiers, go-to resource for expert guidance on cable glands, covering everything from basic selection and installation to advanced hazardous area solutions.

HAVE A QUESTION?

We pride ourselves on our superior customer service and knowledge

REQUEST A CATALOGUE